Style Variant 58021, Double-sided, 17 m

  • Viewing distance: 17 meters
  • Double-sided
  • Light source: 8W/T16
  • Protection class 2
  • Degree of protection: IP41
  • Degree of protection: IP54
  • According to DIN4844
  • CGLine Technology
Style Variant 58021, Double-sided, 17 m

With a viewing distance of 17 m and a pictograms foil set, the Style Variant luminaire is suitable for a wide spectrum of applications. IP54 versions are also optionally available for increased tightness requirements indoors or in canopied outdoor areas. The luminaire is available with a rated operating duration of one or three hours according to application.

Documents
Data sheet (731 KB) (PDF)
Tender text (28 KB) (MSWORD)
Images
Download file (237 KB) (JPEG)

No longer available

Viewing distance 17 m
Luminous flux ΦE/Φnom at end of rated operating time 40%
Housing material Polycarbonate (850 °C glow wire resistant)
Housing colour Light grey, sim. RAL 7035
Weight 58021-1/D: 1.30 kg, 58021-3/D: 1.55 kg
Type of mounting Wall or ceiling mounting
Terminals Mains connection 3 x 2.5 mm² / Bus connection 2 x 1.5 mm²
Connection voltage 230 V AC, 50 Hz
Power consumption mains operation (apparent power/effective power) 16 VA
Permissible ambient temperature Maintained mode -5 °C to +30 °C, Non-maintained mode 0 °C to +35 °C 
Battery Rated operating time 1 h: NC-Accu 3.6 V / 1.5 Ah, Rated operating time 3 h: NC-Accu 3.6 V / 4.0 Ah
Light source 8W/T16, 450 lm
Degree of protection IP41 / IP54
Insulation class ll

 

Features

  • Self-monitoring self-contained luminaire for stand-alone operation or for connection to the central monitoring device CG Controller CGLine 400 or PC-Interface
  • Test results with fault analysis (lamps, charging and battery circuit) as well as status displays (operation, function test, duration test) via 3 coloured LEDs
  • Optional IP54 set for increased sealing requirements for indoor rooms or for canopied outdoor areas
  • Automatic function test (weekly) and duration test (every 3 months)
  • Manual function test or operational duration test via testing buttons
  • Automatic charging monitoring and deep discharge protection with restart inhibit
  • No-load and short-circuit shut-down of the inverter
  • 1 minute delay of normal mode after mains returns (acc. to DIN VDE 0100-718)
  • Blocking function with CG-Controller CGLine 400 or PC-Interface in times of shut-down
  • Luminaires are generally suitable for maintained or non-maintained mode