Sorry, you need to enable JavaScript to visit this website.

Style Variant 28021 LED, Double-sided, 32 m

  • Viewing distance: 32 meters
  • Light source: LED
  • Protection class 2
  • Degree of protection: IP41
  • According to DIN4844
  • CGLine Technology
Style Variant 28021 LED, Double-sided, 32 m

With a viewing distance of 32 m and a pictograms foil set, the Style Variant luminaire is suitable for a wide spectrum of applications. LED technology significantly reduces energy consumption. In addition, maintenance effort is reduced to a minimum thanks to the high LED service life of 50,000 hours. One or three hours rated operating duration can be freely specified according to application.

Documents
Data sheet (754 KB) (PDF)
Tender text (30 KB) (MSWORD)
Images
Download file (317 KB) (JPEG)

No longer available

Viewing distance 32 m
Luminous flux ΦE/Φnom at end of rated operating time 50% 1 h, 20% 3 h
Housing material Polycarbonate (850 °C glow wire resistant)
Housing colour Light grey, sim. RAL 7035
Weight 1.2 kg
Type of mounting Ceiling mounting
Terminals Mains connection 3 x 2.5 mm² / Bus connection 2 x 1.5 mm²
Connection voltage 230 V AC, 50 Hz
Power consumption mains operation 11.0 VA
Permissible ambient temperature Maintained mode -5 °C to +30 °C, Non-maintained mode 0 °C to +35 °C 
Battery Maintanance free and gas tight, NiMh 4.8 V / 1.1 Ah
Light source 4 x HighPower LEDs
Degree of protection IP41
Insulation class ll

 

Features

  • Self-monitoring self-contained luminaire for stand-alone operation or for connection to the central monitoring device CG Controller CGLine 400 or PC-Interface
  • Test results with fault analysis (lamps, charging and battery circuit) as well as status display (operation, function test, duration test) via 3 coloured LEDs
  • Automatic function test (weekly) and duration test (every 3 months)
  • Manual function test or operational duration test via testing buttons
  • Automatic charging monitoring and deep discharge protection with restart inhibit
  • No-load and short-circuit shut-down of the inverter
  • 1 minute delay of normal mode after mains returns (acc. to DIN VDE 0100-718)
  • Blocking function with CG Controller CGLine 400 or PC interface in times of shut-down
  • Luminaires are generally suitable for maintained or non-maintained mode