Sorry, you need to enable JavaScript to visit this website.

Style Industry 48011, LED, Single-sided, 32 m

  • Viewing distance: 32 meters
  • Single-sided
  • Light source: LED
  • Protection class 1
  • Degree of protection: IP41
  • Degree of protection: IP54
  • According to DIN4844
  • CGLine Technology
Style Industry 48011, LED, Single-sided, 32 m

Style Industry with its robust diecast aluminium housing is also highly dependable in challenging ambient conditions. IP54 versions are also optionally available for increased tightness requirements indoors or in canopied outdoor areas. LED technology significantly reduces energy consumption. In addition, maintenance effort is reduced to a minimum thanks to the high LED service life of 50,000 hours. One or three hours rated operating duration can be freely specified according to application.

Documents
Data sheet (630 KB) (PDF)
Tender text (30 KB) (MSWORD)
Images
Download file (313 KB) (JPEG)

No longer available

Viewing distance 32 m
Luminous flux ΦE/Φnom at end of rated operating time 50 % at 1 h, 20 % at 3 h
Housing material Aluminium
Housing colour Light grey, sim. RAL 7035
Weight IP41: 2.2 kg, IP54: 3.0 kg
Type of mounting Wall mounting
Terminals Mains connection 3 x 2.5 mm² / Bus connection 2 x 1.5 mm²
Connection voltage 230 V AC, 50 Hz
Power consumption mains operation 6.4 VA
Permissible ambient temperature Maintained mode -5 °C to +30 °C, Non-maintained mode 0 °C to +35 °C 
Battery maintenance free and gas tight NiMh 4.8 V / 1.1 Ah
Light source 3 x HighPower LEDs
Degree of protection IP41 / IP54
Insulation class l

 

Features

  • Self-monitoring LED self-contained luminaire for stand-alone operation or for connection to the central monitoring device CG Controller CGLine 400 or PC-Interface
  • Selectable operating time 1 h or 3 h
  • Minimum service requirement due to high service life of the LEDs (50,000 hours)
  • Brightness selectable in 3 steps
  • Test results with fault analysis (lamps, charging and battery circuit) as well as status displays (operation, function test, duration test) via 3 coloured LEDs
  • Automatic function test (weekly) and duration test (every 3 months)
  • Manual function test or operational duration test via testing buttons
  • Automatic charging monitoring and deep discharge protection with restart inhibit
  • 1 minute delay of normal mode after mains returns (acc. to DIN VDE 0100-718)
  • Blocking function with CG-Controller CGLine 400 or PC-Interface in times of shut-down
  • Luminaires are generally suitable for maintained or non-maintained mode