Sorry, you need to enable JavaScript to visit this website.

External TLS-Bus Module

External TLS-Bus Module

The TLS bus module is used to poll stairwell light switches, to supply the glow lamps in mains and emergency operation and for the common switching of safety and general lighting. The housing is suitable for DIN rail mounting. General and safety luminaires can be controlled via the same push buttons with use of a TLS switching module (installation in light distributor). The module has a service button, an RS 485 bus port (integral 120 Ohm bus load resistor), 24 V module supply, and generates the glow lamp voltage. It also has a glow lamp flash function (30 s before On-time timeout). The TLS bus module is addressed with encoding switches. Coloured LEDs indicate fault, ON status and operation. Freely programmable assignment of independent TLS inputs per emergency light circuit and individual name per bus module in control unit.

Documents
Data sheet (81 KB) (PDF)
Tender text (9 KB) (ZIP)
Images
Download file (654 KB) (JPEG)
Supply voltage device 24 V DC (min. 19 V, max. 30 V)
Current consumption at 24 V Standby 10 mA ± 3 mA, 1 pushed push-button 35 mA ± 5 mA, 2 pushed push-button 60 mA ± 6 mA
Degree of protection IP20
Insulation class I
Ambient temperature -10 °C to +40 °C
Connection T1/T2 max. 50 mA each, z. B. 50 push-button with glow lamp 1 mA
Connection K1/K2 10 A/250 V AC starting current max. 120 A/ms
Data bus RS 485
Address range 1-25
Weight 0.2 kg
Dimensions (L x W x H) mm 105 x 85 x 60
Montage DIN-rail
Connection terminals/plug-in terminals 2.5 mm² rigid and flexible
Number of button inputs 2 pcs. incl. supply the glow lamp (max. 50 mA)
Load circuits for general lighting 2 Stück (10 A/120 A/ms)
Variable on-time 1 bis 15 min.

 

Features