Sorry, you need to enable JavaScript to visit this website.

External 3-PM-IO und CEAG 3-PM-IO-INV module

External 3-PM-IO und CEAG 3-PM-IO-INV module

To avoid risks from mains failures, it is necessary to permanently monitor the function of the general lighting light distributors in order to switch on the safety lighting in the event of a fault. Thus, the CEAG 3-PM-IO and CEAG 3-PM-IO-INV modules are an important part of the safety system.

Documents
Tender text 3-PM-IO (24 KB) (MSWORD)
Tender text 3-PM-IO-INV (24 KB) (MSWORD)
Images
Download file (297 KB) (JPEG)
Rated voltage 24 V DC (min. 19 V, max. 30 V)
Current consumption
(all 8 channel connected)
20 mA ± 5 mA
Degree of protection IP 20
Insulation class I
Ambient temperature -10 ° to +40 °C
Input channels 8
3-PM (channel 1-8)
3-PH (channel 1-5)
3-PM-IO:
8 (potential free UN = 230 V)
3-PM (Chan. 1-8) > 195 V -> ON
< 138 V -> OFF
3-PM-IO-INV:
8 (potential free UN = 230 V)
3-PM (Chan. 1-8) < 195 V -> OFF
> 138 V -> ON
Data bus / Address range RS 485 / 1-25
Weight 0.2 kg
Dimensions (L x W x H) mm 105 x 85 x 60
Mounting DIN-Schiene
Connection terminals 2.5 mm2 rigid and flexible

Features

  • Permanent function monitoring of the entire system by bus technology
  • Automatic logging of all test results in the test log book
  • Test button for mains / emergency light failure thus no interruption of the mains voltage necessary and thus no malfunctions of the operational processes
  • 3-PM-IO Modul: Eight measurement inputs for monitoring up to three phases and up to 5 * light switches
  • 3-PM-IO-INV Modul: Eight inverted measurement inputs for monitoring up to three phases and up to 5* light switches
  • Freely configurable assignment of the measuring inputs to the emergency lighting
  • No E30 wiring of bus illumination due to Fail Save Bus technology