Sorry, you need to enable JavaScript to visit this website.

AE-CU-E Installation variant

AE-CU-E Installation variant

Adaptive Evacuation Control Unit for assembly in ZB-S/18-AE units using loop technique for controlling addressable adaptive exit sign luminaires with 230V / 216V AC/DC technology for safety lighting systems acc. to DIN VDE 0100-560, DIN EN 50172 and V DIN V VDE 0108-100. With automatic testing device and monitoring of loop bus communication and individual display of condition and name of loop BUS connection per GuideLed DXC luminaire.

Documents
Data sheet (167 KB) (PDF)
Tender text (35 KB) (MSWORD)
Images
Download file (314 KB) (JPEG)
Primary rated voltage 28.5 V / DC
Primary rated current 4.2 A
Protection rating IP 20
Insulation class I
Ambient temperature -5°C to +40°C
Secondary rated voltage 18.5 V - 29.6 V
Weight 8 kg
Dimensions (HxWxD in mm) 200 x 500 x 190
Material Sheet steel, powder-coated
Inputs  
Addressable loop line 4
Scenario active inputs 2 (more on request)
Maximum ring length 2,000 m / I(ST)Y 4 x 2 x 0.8 mm
Maximum number of GuideLed DX/DXC luminaires per loop 60
Outputs  
Zero-potential changeover contact 2
Contact load 24 V / 1 A
Fuse 1.35 A

 

 
 
 

Features

  • AE-CU for the adaptive control of up to 240 GuideLed DXC luminaires
  • Four short circuit and open circuit resistant loop lines each with 60 GuideLED DXC luminaires
  • Two scenarios freely programmable for building evacuation, factory provided integrated
  • More than two scenarios on request
  • A maximum of six ZB-S/US-S systems can be connected per AE-CU. More than six ZB-S systems on request
  • Automatic software address-setting of all GuideLed DXC luminaires for scenario control