Sorry, you need to enable JavaScript to visit this website.

V-CG-SB.1 with DALI Control Input

  • Degree of protection: IP20
  • ENEC certified
  • With STAR Technology
  • With STAR Plus Technology
V-CG-SB.1 with DALI Control Input

Emergency luminaire monitoring module with 20 addresses for function monitoring (CEWA GUARD Technology) of a DALI control gear or LED supply and switching modes (maintained/non-maintained and switched emergency luminaires) freely programmable in one circuit without additional data line to the luminaires in conjunction with suitable emergency lighting systems (with STAR-Technology).
Adjustable luminous flux relation in DC mode in 10 % steps between 10 % and 100 % for reduction of the needed battery capacity.

Rated voltage ranges 220 - 240 V, 50/60 Hz / 176 - 275 V DC
Standby power loss < 1 W (230 V / 50 Hz)
Connection DALI electronic control gear or LED supply
Maximum distance 1 m (module - DALI-ECG / LED driver)
Type of mounting To be mounted in luminaires with protection category I or II
Degree of protection IP20
Permissible ambient temperature ta = -20 °C to +60 °C
Maximal permissible test point temperature tc = 65 °C
Connection terminals mains Plug in terminal 2.5 mm² / reserve-polarity protected
Connection terminals DALI-BUS Plug in terminal 1.5 mm² / reserve-polarity protected
Dimensions in mm ( H x L x W) 21 x 145 x 30
Housing material / colour Flame retardant polycarbonate / grey
Weight 0.047 kg
Adjustable luminous flux relation in DC mode 10 % - 100 % (in 10 %-steps)

 

Features

  • Low operating costs due to decreased standby losses < 1 W
  • Minimized dimensions on the basis of conventional T5 EVG cross section (H x W: 21 x 30 mm) for an eased mounting in narrow luminaires
  • Variable mounting possibilities for different mounting positions (horizontal or sidewise upright)
  • Avoidance of installation failures due to a mains connection being protected against polarity reversal
  • Universal monitoring module for all DALI electronic control gears / LED supplies
  • Shortened inspection effort due to the CEWA GUARD and S+ Technology: Automatic function monitoring of up to 20 luminaires per circuit
  • Reduced installation costs due to STAR-Technology: Freely programmable mixed operation of the switching modes per luminaire in one circuit
  • Reduced installation expenditures as no additional data line to the luminaires is needed
  • Enlarged ambient temperature range
  • Safe galvanic isolation of the bus systems (emergency lighting / mains lighting during emergency    operation)
  • Adjustable luminous flux relation in DC mode in steps between 10 % and 100 %