V-CG-S2 1,5-30 W

  • Degree of protection: IP20
  • ENEC certified
  • With STAR Technology
  • With STAR Plus Technology
V-CG-S2 1,5-30 W

Emergency luminaire monitoring module with 20 addresses for function monitoring (CEWA GUARD Technology) of loads between 1,5-30 W (fluorescent lamps with high frequency electronic ballast) and switching modes (maintained/non-maintained and switched emergency luminaires) freely programmable in one circuit without additional data line to the luminaires in conjunction with suitable emergency lighting systems (with STAR-Technology).

Connection voltage 220 - 240 V, 50/60 Hz / 176 - 275 V DC
Standby power loss < 0.5 W (230 V / 50 Hz)
Power input 1.5 W - 30 W
Maximum line length 50 m (module - luminaire)
Type of mounting To be mounted in luminaires with protection category I or II
Degree of protection IP20
Permissible ambient temperature ta = -20 °C to +60 °C
Maximal permissible test point temperature tc = 75 °C
Terminals Clamp terminal 2.5 mm² / reserve-polarity protected
Dimensions in mm ( H x L x W) 21 x 85 x 30
Housing material / colour Flame retardant polycarbonate / grey
Weight 0.035 kg
Max. permitted inrush current 30 A

Features

  • Low operating costs due to decreased standby losses < 0.5 W
  • Minimized dimensions on the basis of conventional T5 EVG cross section (H x W: 21 x 30 mm) for an eased mounting in narrow luminaires
  • Without protective conductor connection. For the use in luminaires with insulation class I or II
  • Variable mounting possibilities for different mounting positions (horizontal or sidewise upright)
  • Avoidance of installation failures due to a mains connection being protected against polarity reversal
  • Universal monitoring module for loads 1.5 – 30 W
  • Shortened inspection effort due to the CEWA GUARD and S+ Technology: Automatic function monitoring of up to 20 luminaires per circuit
  • Reduced installation costs due to STAR-Technology: Freely programmable mixed operation of the switching modes per luminaire in one circuit
  • Reduced installation expenditures as no additional data line to the luminaire is needed
  • Enlarged ambient temperature range