V-CG-SLS 28
- Degree of protection: IP20
- ENEC certified
- With STAR Technology
- With STAR Plus Technology

LED Supply- and Monitoring module for a LED strip with own current control for 28 V DC and 20 addresses for function monitoring (CEWA GUARD Technology) and switching modes (maintained/non-maintained and switched mode) freely programmable in one circuit without additional data line to the luminaires in conjunction with suitable emergency lighting systems (with STAR-Technology).
Documents
Data sheet (314 KB) (PDF)
Mounting and operating instructions (274 KB) (PDF)
General safety instructions for modules (194 KB) (PDF)
Declaration of conformity (1 MB) (PDF)
3rd Party Certification - ENEC (2 MB) (PDF)
Images
Download file (248 KB) (JPEG)
Primary side | |
Connection voltage | 220 - 240 V, 50/60 Hz / 176 - 275 V DC |
Standby power loss | < 0.5 W (230 V / 50 Hz) |
Current consumption | 35 mA (230 V AC) / 20 mA (220 V DC) |
Power consumption | 8.1 VA (230 V AC) |
Power factor λ | 0.45 ... 0.60 |
Inrush current | ≤ 1.5 A |
Operating frequency | 132 kHz |
EEI | A2 |
Terminals | Clamp terminal 2.5 mm² / reserve-polarity protected |
Secondary side | |
Output current | 110 mA (Maximum current) |
Output voltage | 28 V DC (Constant voltage) |
Lamp load | LED strip with own current control for 28 V DC and max. 110 mA |
Output power (max.) | 3.1 W |
Terminals | Clamp terminals 1.5 mm² / not reserve-polarity protected |
Maximum line length | 1 m (Modul – LED) |
Type of mounting | To be mounted in luminaires with protection category I or II |
Degree of protection | IP20 |
Permissible ambient temperature | ta = -20 °C to +50 °C |
Maximal permissible test point temperature | tc = 70 °C |
Dimensions in mm ( H x L x W) | 21 x 110 x 30 |
Housing material / colour | Flame retardant polycarbonate / grey |
Weight | 0.042 kg |
Luminous flux ΦE/Φnom at the end of rated operating time | 100 % |
Features
- Low operating costs due to decreased standby losses < 0.5 W
- Minimized dimensions on the basis of conventional T5 LCG cross section (H x W: 21 x 30 mm) for an eased mounting in narrow luminaires
- Without protective conductor connection. For the use in luminaires with insulation class I or II
- Variable mounting possibilities for different mounting positions (horizontal or sidewise upright)
- Avoidance of installation failures due to a mains connection being protected against polarity reversal
- Shortened inspection effort due to the CEWA GUARD Technology: Automatic function monitoring of up to 20 luminaires per circuit
- Reduced installation costs due to STAR-Technology: Freely programmable mixed operation of the switching modes per luminaire in one circuit
- Reduced installation expenditures as no additional data line to the luminaires is needed