Sorry, you need to enable JavaScript to visit this website.

Linear Fluorescent Luminaire eLLk CG-S

  • Protection class 1
  • Degree of protection: IP66
  • According to EN1838
  • Explosion protected
  • With STAR Technology
  • With STAR Plus Technology
Linear Fluorescent Luminaire eLLk CG-S

The explosion-protected linear luminaires are approved for areas with gas explosion-hazard zones 1 and 21 as well as dust explosion-hazard zones 21 and 22, according to the APEX 94/9/EG directive. With a high IP66 protection rating and a robust housing they are ideal for use in industrial environments. The completely monitored linear luminaires are equipped with energy-saving dual-channel ECGs This ensures that with failure of a lamp the second lamp remains independently in operation.

Documents
Data sheet (1 MB) (PDF)
Tender text (27 KB) (MSWORD)
Images
Download file (185 KB) (JPEG)
Marking acc. to 94/9/EG Ex II 2G Ex de mb IIC T4 Gb, Ex II 2D Ex tb IIIC T80 °C Db IP66 
EU-type inspection certificate BVS 09 ATEX E 034
IECEx-inspection certificate IECEX BVS 09.0033
Marking acc. to IECEx Ex de mb IIC T4 Gb, Ex tb IIIC T80 °C Db
Housing material glass-fibre reinforced polyester
Protective bowl Polycarbonate
Rated voltage AC: 220-254 V 50/60 Hz, DC: 195-250 V
Circuit EVG / CG-S
Rated current 0.19 A (eLLK 92018/18), 0.35 A (eLLK 92036/36), 0.54 A (eLLK 92058/58)
Leistungsfaktor cos   ≥ 0.95
Permissible ambient temperature -25 °C to + 55 °C (eLLK 92018/18 and eLLK 92036/36)
-25 °C to + 40 °C (eLLK 92058/58)
Cable infeeds Ex e-cable infeeds M25 x 1.5 (Plastic) for cables Ø 8 - 17 mm
Terminals L1, L2, L3, L, N, PE; max. 2 x 6 mm² single wire per terminal
Light source Bi-pin lamp: 18 W, 36 W, 58 W Socket G13
Weight approx. 5.6 kg (eLLK 92018/18), approx. 7.7 kg (eLLK 92036/36), approx. 9.6 kg (eLLK 92058/58)
Degree of protection IP66
Insulation class l

 

Features

  • Completely monitored explosion-protected light fittings
  • Single lamp operation during DC power supply (emergency operation)
  • Enclosure made of reinforced polyester
  • Double ended through-wiring with Ex-e cable infeeds for double-ended cable connection
  • Shortened inspection effort due to CEWA GUARD technology
  • Automatic function monitoring of up to 20 luminaires per circuit
  • Reduced installation expenditure with STAR technology
  • Freely programmable mixed operation of the switching modes per luminaire in one circuit