Sorry, you need to enable JavaScript to visit this website.

8811, SL, Recessed Ceiling Mounting

  • Light source: 8W/T16
  • Protection class 1
  • Degree of protection: IP20
  • According to EN1838
  • CGLine Technology
8811, SL, Recessed Ceiling Mounting

The 8811 CGLine escape luminaire for ceiling recessing enables discreet integration of the escape lighting into its surroundings. Lighting technology is a combination of reflectors and a prismatic cover to ensure wide light point spacing of up to 12 m. The luminaire is available with a rated operating duration of one or three hours according to application.

Documents
Data sheet (551 KB) (PDF)
Tender text (24 KB) (MSWORD)
Images
Download file (396 KB) (JPEG)

No longer available

Luminous flux ΦE/Φnom at end of rated operating time 40%
Housing material Sheet steel
Housing colour RAL 9010
Weight Rated operating time 1 h:  1.9 kg, Rated operating time 3 h:  2.1 kg
Type of mounting Ceiling recessing
Terminals for 2.5 mm²
Connection voltage 230 V AC, 50 Hz
Power consumption mains operation (apparent power/effective power) 16 VA
Permissible ambient temperature Maintained mode -5 °C to +30 °C, Non-maintained mode 0 °C to +35 °C 
Battery Rated operating time 1 h: NC-Accu 3.6V / 1.5 Ah, Rated operating time 3 h: NC-Accu 3.6V / 4.0 Ah
Light source 8W/T16, 450 lm
Degree of protection IP20
Insulation class l

 

Features

  • Self-monitoring self-contained luminaire for stand-alone operation or for connection to the central monitoring device CG Controller CGLine 400 or PC-Interface
  • Test results with fault analysis (lamps, charging and battery circuit) as well as status displays (operation, function test, duration test) via 3 coloured LEDs
  • Automatic function test (weekly) and duration test (every 3 months)
  • Manual function test or operational duration test via testing buttons
  • Automatic charging monitoring and deep discharge protection with restart inhibit
  • No-load and short-circuit shut-down of the inverter
  • 1 minute delay of normal mode after mains returns (acc. to DIN VDE 0100-718)
  • Blocking function with CG-Controller CGLine 400 or PC-Interface in times of shut-down
  • Luminaires are generally suitable for maintained or non-maintained mode